Keywords |
Apartment ; Multidrop chamber ; Ventilation rate ; Distributing the air volume ; Indoor air quality ; Air flow |
Abstract |
The purpose of this study is to evaluate performance of Multidrop Chamber Ventilation System compared Duct Distributer without guide vane in Apartment. The experiments were designed to simulate apartment of 84.88 m2 and 79.9 m2. In additional two cases established multidrop chamber duct and duct distributer without guide vane on the ceiling of the apartment. Distribution performance of air supply rate were evaluated in this experiments. As a result, distribution performance of air supply rate in the duct distributer without guide vane is different from designed air supply rate by about 74% in case1 and about 40% in case2. However distribution performance of air supply rate in the multidrop chamber with guide vane is different from designed air supply rate by about 98~99% in case1 and case2. Therefore, the multidrop chamber system is considered to satisfy proper air supply rate of each room in Apartment Houses. |