1. Introduction

Nowadays, many studies are carried out on the subject of renewable electricity generation from the sun, wind, etc. since traditional energy-generating stations rely on fossil fuels, which will be exhausted soon. Unbalanced linear and nonlinear loads cause distorted load current, which affects the voltage profile of a weak grid formed by standalone REPS [1]. A grid-connected VSI and advanced control techniques are essential for the effective integration of REPS with a weak distribution grid [2,3]. Other PQ issues in a weak grid are harmonics, imbalance, reactive power demand, islanding, etc. Due to these PQ problems, the voltage at PCC of VSI is distorted.

Shunt Active Filters (SAF) provide a better solution for current related PQ issues. Among custom power devices, DSTATCOM is efficient at mitigating PQ problems like imbalance, harmonics, and reactive power demand in the distribution network. Various conventional and modern control techniques of DSTATCOM are referenced in the literature, such as synchronous reference frame theory (SRFT) [4], instantaneous reactive power theory (IRPT) [5], instantaneous symmetrical component theory (ISCT) [6], Least Mean Square-based control algorithm [7], Combined least mean square-least mean fourth (LMS-LMF) based control algorithm [8], and so on.

It is essential to calculate the positive sequence, frequency, and phase angle of PCC (supply) voltages to provide precise compensating current in a weak grid. To follow the phase angle of PCC voltage, different PLL methods with improved filtering capabilities were developed [9]. A conventional PLL is based on synchronous reference frame theory (SRF-PLL), which uses a moving average filter (MAF) of specified window results slower dynamic response [10]. Various PLL-based methods referenced in the literature are generally used to estimate phase and frequency in a weak grid, such as dual SRF-PLL (DSRF-PLL) [11], complex coefficient filter-PLL (CCF-PLL) [12], multiple complex coefficient filter-PLL (MCCF-PLL) [13], second-order generalized integrator-PLL (SOGI-PLL) [14], and so on. Dual SOGI-PLL can also be used as a pre-filter to calculate the positive sequence of supply voltages [15]. The SOGI of PLL was tuned using estimated frequency to determine the positive sequence of supply voltages, which leads to codependency and makes the system unstable with a high-speed PI controller. Recalculating the error and tuning the DSOGI pre-filter with a fixed center frequency is also feasible [16-18].

This paper presents a control technique based on a frequency-fixed DSOGIPLL (FFDSOGI-PLL) for DSTATCOM to compensate for a system with nonlinear load under weak grid conditions. The FFDSOGI-PLL was designed for estimating the positive sequence of supply voltages from which the unit templates of PCC voltages are determined. These unit templates are used to generate compensating current using the SOGI block. A hysteresis current controller (HCC) is used to produce gate pulses for the VSI switches. The detailed analysis of the FFDSOGI-PLL-based DSTATCOM is shown in the following sections.

2. Proposed System

Fig. 1 shows the TPFW structure of the distribution network with a linear and nonlinear load. The supply distortion is increased due to the flow of distorted load current through the system impedance. The load, DSTATCOM, zig-zag transformer for neutral current compensation, and the supply are connected at PCC. By processing voltages and currents sensed at various places, the gating pulses for VSI are generated, and the DSTATCOM injects compensating current at PCC to improve power quality.

Fig. 1. FFDSOGI-PLL control technique for DSTATCOM in TPFW system.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig1.png

Fig. 1 also shows the FFDSOGI-based control algorithm for PQ enhancement in a TPFW system with both unbalanced linear and nonlinear loads. The load current is unbalanced and distorted. Since the same load current flows through the system impedance, PCC voltages also become unbalanced and distorted. Therefore, the templates taken from PCC voltages are not suitable for direct use as a reference for synchronization and generation of a reference for DSTATCOM. Hence, the FFDSOGI-PLL-based control technique is used to extract the positive sequence of PCC voltages.

Initially, the PCC voltages are converted to ${\alpha}$${\beta}$ components:

(1)
$\left[\begin{array}{l} v_{t\alpha }\\ v_{t\beta } \end{array}\right]$=$\sqrt{\frac{2}{3}}\left[\begin{array}{lll} 1 & -\frac{1}{2} & -\frac{1}{2}\\ 0 & \frac{\sqrt{3}}{2} & -\frac{\sqrt{3}}{2} \end{array}\right]\left[\begin{array}{l} v_{ta}\\ v_{tb}\\ v_{tc} \end{array}\right]$

where $v_{ta},\,\,v_{tb},$ and $v_{tc}$ are the PCC voltages, and $v_{t\alpha }$ and $v_{t\beta }$ are the ${\alpha}$${\beta}$ components of transformed voltages. The transformed voltages can also be written as:

(2)
$ \begin{equation} v_{t\alpha \beta }^{h}=v_{t\alpha \beta }^{h+}+v_{t\alpha \beta }^{h-}+v_{t\alpha \beta }^{h0} \end{equation} $

where h is the harmonic order. To calculate the fundamental positive sequence for ${\alpha}$${\beta}$ elements of PCC voltages $v_{t\alpha \beta }^{+}$, FFDSOGI is tuned to a fundamental frequency of 50 Hz, which is free from negative sequence components and all harmonics. Then, it is transformed to obtain positive sequence voltages $v_{\textit{tabcf}}^{+}$ .

(3)
$\left[\begin{array}{l} v_{taf}^{+}\\ v_{tbf}^{+}\\ v_{tcf}^{+} \end{array}\right]$=$\sqrt{\frac{2}{3}}\left[\begin{array}{ll} 1 & 0\\ -\frac{1}{2} & \frac{\sqrt{3}}{2}\\ -\frac{1}{2} & -\frac{\sqrt{3}}{2} \end{array}\right]\left[\begin{array}{l} v_{t\alpha }^{+}\\ v_{t\beta }^{+}\\ v_{to} \end{array}\right]$

Then, the unit templates are extracted using the positive sequence voltages and processed with fundamental active components of the load current to determine the reference currents.

3. Modelling and Analysis of FFDSOGI-PLL

SOGI is basically a frequency adaptive prefilter. The output signal of SOGI represents the fundamental component of PCC voltages if the SOGI center frequency $\hat{\omega }$ is tuned to grid frequency $\omega $. Fig. 2 shows SOGI's fundamental framework.

If the input of $v\left(t\right)=\sin \omega t$ is applied, the following expressions are obtained:

(4)
$$ \begin{aligned} v^{\prime}(t)=& \frac{k \omega \hat{\omega}}{\sqrt{k^2 \hat{\omega}^2 \omega^2+\left(\hat{\omega}^2-\omega^2\right)^2}}(\sin (\omega t-\delta)-\\ &\left.\operatorname{Asin}\left(\frac{\sqrt{1-k^2}}{4} \hat{\omega} t-\Phi_1\right) e^{\frac{-k \hat{\omega} t}{2}}\right) \end{aligned} $$
(5)
$$ \begin{aligned} &q v^{\prime}(t)=\frac{-k \hat{\omega}^2}{\sqrt{k^2 \hat{\omega}^2 \omega^2+\left(\hat{\omega}^2-\omega^2\right)^2}}(\cos (\omega t-\delta)+A\\ &\left.\cos \left(\frac{\sqrt{1-k^2}}{4} \hat{\omega} t-\Phi_2\right) e^{\frac{-k \hat{\omega} t}{2}}\right) \end{aligned} $$
(6)
$$ \sin (\delta)=\frac{\omega^2-\hat{\omega}^2}{\sqrt{k^2 \hat{\omega}^2 \omega^2+\left(\hat{\omega}^2-\omega^2\right)^2}} $$
(7)
$$ A=\frac{k \omega \hat{\omega}}{\sqrt{k^2 \hat{\omega}^2 \omega^2+\left(\omega^2-\hat{\omega}^2\right)^2} \sqrt{1-k^2} / 4} $$

After a transient decade under the locked condition in the above equations, the output is equal to the input for Eq. (4), and the output is orthogonal to the input for Eq. (5). The amplitude of the output will be decreased if the input has a high-frequency component (harmonics).

In the FFDSOGI-PLL, the tuning frequency is different from the SOGI’s tuning frequency. In other studies [15,16], an FFDSOGI-PLL was applied for single-phase and 3-phase systems. Here, the nominal frequency$\omega _{0}$ (50Hz) was chosen as the tuning frequency of the FFDSOGI-PLL instead of $\hat{\omega }$ and substituted in Eqs. (4)-(7). From the equation above, if the grid frequency $\omega $ deviates from the nominal frequency $\omega _{0}$,the amplitude and phase angle of the output signal differ. For the given input of $v_{\alpha }\left(t\right)=\sin \omega t$and $v_{\beta }\left(t\right)=-\cos \omega t$, the output of the FFDSOGI-PLL after transient decay is as follows:

(8)
$$ v_{F F, \alpha}^{\prime}(t)=\frac{k \omega \omega_o}{\sqrt{k^2 \omega_0^2 \omega^2+\left(\omega_0^2-\omega^2\right)^2}} \sin \left(\omega t-\delta_{F F}\right) $$
(9)
$$ q v_{F F, \alpha}^{\prime}(t)=\frac{-k \omega_0^2}{\sqrt{k^2 \omega_0^2 \omega^2+\left(\omega_0^2-\omega^2\right)^2}} \cos \left(\omega t-\delta_{F F}\right) $$

and

(10)
$$ v_{F F, \beta}^{\prime}(t)=\frac{-k \omega \omega_o}{\sqrt{k^2 \omega_0^2 \omega^2+\left(\omega_0^2-\omega^2\right)^2}} \cos \left(\omega t-\delta_{F F}\right) $$
(11)
$$ q v_{F F, \beta}^{\prime}(t)=\frac{-k \omega_0^2}{\sqrt{k^2 \omega_0^2 \omega^2+\left(\omega_0^2-\omega^2\right)^2}} \sin \left(\omega t-\delta_{F F}\right) $$

with

(12)
$ \sin \left(\delta _{FF}\right)=\frac{\omega ^{2}-\omega _{0}^{2}}{\sqrt{k^{2}\omega _{0}^{2}\omega ^{2}+\left(\omega _{0}^{2}-\omega ^{2}\right)^{2}}} $

Since the signals above require equal amplitude, they are modified by multiplying $v_{FF,\alpha }^{'}\left(t\right)$ and $qv_{FF,\beta }^{'}\left(t\right)$ with $\frac{\hat{\omega }}{\omega _{0}}$. Hence, the second harmonic ripple in $v_{d}\left(t\right)$ and $v_{q}\left(t\right)$ is reduced. If $\omega $ deviates from $\omega _{0}$, it is phase-shifted by $\delta _{FF}$ as in Eq. (9). This phase shift is present in the SRF-PLL input signals $v_{\alpha ,\epsilon }^{+}\left(t\right)$ and $v_{\beta ,\epsilon }^{+}\left(t\right)$ even after the positive sequence has been determined.

(13)
$$ \left[\begin{array}{c} v_{\alpha, d}^{+} \\ v_{\beta, \delta}^{+} \end{array}\right]=\left[\begin{array}{cc} v_{F F, \alpha}^{\prime} & -q v_{F F, \beta}^{\prime} \\ v_{F F, \beta}^{\prime} & q v_{F F, \alpha}^{\prime} \end{array}\right]\left[\begin{array}{c} 1 \\ \hat{\omega} \\ \omega_o \end{array}\right] $$

As a result of the phase angle $\theta _{\epsilon }$ changing,the calculated grid voltage’s phase angle must be compared to the projected phase angle, $\theta =~ \omega t$. Eq. (12) is modified for a small drift of $\omega $ from $\omega _{0}$ as follows:

(14)
$ \delta _{FF}\approx \frac{\omega ^{2}-\omega _{0}^{2}}{k\omega \omega _{o}} $

Hence, the estimated phase angle is corrected to the actual value by:

(15)
$\hat{\theta }$=$\widehat{\theta _{e}}+\delta _{FF}$

The amplitude and phase angle correction using FFDSOGI are shown in Fig. 3. It should be noted that feeding $\omega $ into the multiplication for amplitude modification has a different effect than using it to tune both SOGI filters. Because of the stability, an additional low pass filter could be added to the SRF-PLL, which reduces harmonics in the output signals.

Fig. 2. Basic structure of SOGI2.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig2.png
Fig. 3. FFDSOGI-PLL with an estimation of positive sequence.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig3.png

4. Determination of Symmetrical Components using FFDSOGI-PLL

It is easier to separate the positive sequence from harmonics compared to a negative or zero sequence. However, the supply voltage has a higher harmonic content and is unbalanced, and the magnitude of the positive sequence is larger than in other sequences. As a result, a filter with a robust damping property is required. A low $k$ factor is needed for good harmonic mitigation with the SOGI configuration. But the low $k$factorcauses the PLL's dynamic response to be slower. The mechanism is more robust when the tuning frequency is decoupled in the FFDSOGI-PLL, allowing for a high-speed PI controller. Hence, an increased natural frequency$\omega _{n}$was selected to tune it. It is possible to achieve better harmonic damping with a faster settling time.

4.1 Positive Sequence Calculation

The output of the FFDSOGI structure with amplitude adjustment and after the transient component decaying up to $\omega =\hat{\omega }$ has four essential componentswith a phase displacement of $\delta _{FF}$ and reduction in amplitude of:

(16)
$K_{\epsilon }$=$\frac{-k\omega _{o}\hat{\omega }}{\sqrt{k^{2}\hat{\omega }^{2}\omega _{0}^{2}+(\omega _{0}^{2}-\hat{\omega }^{2})^{2}}}$

This reduction in the amplitude is nullified by multiplying with its reciprocal amplitude. The error in phase angle $\theta _{\epsilon }$ is minimized using Eqs. (14) and (15), which results in the actual phase angle $\hat{\theta }$. $v_{\alpha ,\epsilon }^{+}$ and $v_{\beta ,\epsilon }^{+}$ are transformed to SRF and inversely transformed ($v_{\alpha }^{+}$ and $v_{\beta }^{+}$) using $\theta _{\epsilon }$ and $\hat{\theta }$, respectively, which nullifies the phase error. Also, the DC signal is sent through a low pass filter to improve harmonic damping. It is also possible to calculate the actual phase and amplitude using the equation below.

(17)
$ \begin{equation} \left[\begin{array}{l} v_{\alpha }^{+}\\ v_{\beta }^{+} \end{array}\right]=\frac{1}{K_{\epsilon }}\left[\begin{array}{ll} \cos \left(\delta _{FF}\right) & -\sin \left(\delta _{FF}\right)\\ \sin \left(\delta _{FF}\right) & \cos \left(\delta _{FF}\right) \end{array}\right]\left[\begin{array}{l} v_{\alpha ,\epsilon }^{+}\\ v_{\beta ,\epsilon }^{+} \end{array}\right]~ \end{equation} $

4.2 Negative Sequence Calculation

The negative sequence is determined similarly to the positive sequence by calculating the amplitude and phase-displaced signals using quadrature signals of the FFDSOGI structure.

(18)
$ \begin{equation} \left[\begin{array}{l} v_{\alpha ,\epsilon }^{-}\\ v_{\beta ,\epsilon }^{-} \end{array}\right]=\left[\begin{array}{ll} v_{FF,\alpha }^{'} & qv_{FF,\beta }^{'}\\ -v_{FF,\beta }^{'} & qv_{FF,\alpha }^{'} \end{array}\right]\left[\begin{array}{l} 1\\ \frac{\hat{\omega }}{\omega _{o}} \end{array}\right] \end{equation} $

Similar to the positive sequence, the amplitude and phase displacement are calculated. The amplitude is multiplied by $\frac{1}{K_{\epsilon }}$ and then transformed to SRF. Also, its inverse transformation is calculated.

(19)
$ \begin{equation} \left[\begin{array}{l} v_{\alpha }^{-}\\ v_{\beta }^{-} \end{array}\right]=\frac{1}{K_{\epsilon }}\left[\begin{array}{ll} \cos \left(\delta _{FF}\right) & -\sin \left(\delta _{FF}\right)\\ \sin \left(\delta _{FF}\right) & \cos \left(\delta _{FF}\right) \end{array}\right]\left[\begin{array}{l} v_{\alpha ,\epsilon }^{-}\\ v_{\beta ,\epsilon }^{-} \end{array}\right] \end{equation} $

Fig. 4 shows an estimation of the positive and negative sequences using SRF.

Fig. 4. Compensation for phase and amplitude errors in synchronous reference frame.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig4.png

4.3 Zero Sequence Calculation

The zero sequence signal is determined using Eq. (6) and then filtered using SOGI to separate third-order harmonics. It is tuned with the assessed frequency of the FFDSOGI-PLL instead of tuning it to the fixed frequency with recalculating error.

(20)
$ v_{0}=\frac{1}{3}~ \left(v_{a}+v_{b}+v_{c}\right) $

As shown in Fig. 5, there are two output signals from the SOGI structure.$v'_{0}$ and $qv'_{0}$ are fundamental and quadrature signals of the zero sequence component, respectively. Then, these signals are transformed to SRF with $\hat{\theta }$.

Fig. 5. Filter for zero sequence component.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig5.png

5. FFDSOGI-PLL-based Control Algorithm

Fig. 1 shows the FFDSOGI-PLL-based control algorithm to enhance power quality in a TPFW structure. To build a simple control technique for computing compensator reference signals, the fundamental active components of load currents are determined. The controller modeling process is divided into several phases, which are detailed below.

5.1 Determination of Positive Sequence PCC Voltages

An FFDSOGI-PLL-based filtering technique is used to extract the fundamental positive sequence component of PCC voltages for generating a reference current and synchronization.

5.2 Determination of Active Components of Load Current

The 3-phase load currents’ active components $(m_{a},\,\,m_{b},\,\,m_{c})$ are determined using the structure shown in Fig. 6. The result of SOGI has two quadrature components, which are processed to determine the active components of load currents.

(21)
$ m_{a}=\sqrt{i_{Lap}^{2}+i_{Laq}^{2}} $

Similarly, the load current’s active components of other phases are calculated, and their effective value is determined.

(22)
$ m_{avg}=\frac{m_{a}+m_{b}+m_{c}}{3} $
Fig. 6. SOGI block to determine active component of load currents.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig6.png

5.3 Generation of Gating Pulses

DSTATCOM consists of VSI with a DC-link capacitor, which is able to compensate loads. The power loss $m_{loss}$ in DSTATCOM inevitable since high-frequency switching is involved. To calculate power loss $m_{loss}$, the DC-link voltage reference $V_{dc}^{\mathrm{*}}$ is compared with the measured DC link voltage $V_{dc}$, and a PI controller processes the resulting error. The power loss $m_{loss}$ is described by the following equation:

(23)
$m_{loss}$=$m_{loss}\left(k-1\right)+K_{p}\left\{e_{dc}\left(k\right)-e_{dc}\left(k-1\right)\right\}+K_{I}\left[e_{dc}\left(k\right)\right]$

where

error $e_{dc}\left(k\right)=V_{dc}^{*}\left(k\right)-V_{dc}\left(k\right)$

$K_{p}$ and $K_{I}$ are PI controller gain constants.

The fundamental current magnitude is the sum of $m_{loss}$ and $m_{avg}$, which corresponds to the real power,

(24)
$ m_{f}\left(k\right)=m_{avg}\left(k\right)+m_{loss}\left(k\right) $

The pure sinusoidal and balanced templates of PCC voltages are extracted from distorted PCC voltages using the FFDSOGI-PLL-based system. The peak value $V_{p}$ is determined from the instantaneous PCC voltage templates $\left(v_{taf},\,\,v_{tbf},\,\,v_{tcf}\right)$ as follows:

(25)
$ V_{p}=\frac{2}{3}\sqrt{\left(v_{taf}^{2}+v_{tbf}^{2}+v_{tcf}^{2}\right)} $

The unit templates of PCC voltage$\left(u_{a},\,\,u_{b},\,\,u_{c}\right)$ are:

(26)
$ u_{a}=\frac{v_{taf}}{V_{p}},\,\,u_{b}=\frac{v_{tbf}}{V_{p}},\,\,u_{c}=\frac{v_{tcf}}{V_{p}} $

The fundamental reference supply currents $(i_{sa}^{*},\,\,i_{sb}^{*},\,\,i_{sc}^{*})$ are determined using $m_{f}$ and unit templates:

(27)
$ i_{sa}^{*}=u_{a}xm_{f},\,\,\,\,i_{sb}^{*}=u_{b}xm_{f},\,\,\,\,i_{sc}^{*}=u_{c}xm_{f} $

The reference supply currents above are compared with the 3-phase source current $(i_{sa},\,\,i_{sb},\,\,i_{sc})$ using HCC, and control signals for the VSI switches of DSTATCOM are generated.

6. Results and Discussion

The proposed FFDSOGI-PLL-based DSTATCOM network model was developed in a MATLAB/SIMULINK environment. A 3-phase unbalanced RL load and a 3-phase diode bridge rectifier-fed RL load (nonlinear load) were used. The system is supplied with the right compensation currents via 3-phase 3-wire FFDSOGI-PLL-based DSTATCOM. Both the steady-state and dynamic performance of DSTATCOM was analyzed.

6.1 Steady-state Performance Analysis

The following figures show the steady-state performance of the FFDSOGI-PLL-based DSTATCOM network. The system and load details are given in Table 1.

Figs. 7(a)-(c) show the waveforms of a 3-phase load current$i_{Labc}$, compensator current $i_{fabc}$, and source current $i_{Sabc}$. It shows that even though the load current is unbalanced and nonlinear, the FFDSOGI-PLL-based DSTATCOM balances the source current by injecting the compensator current.

Figs. 8(a) and (b), show the waveforms of PCC voltages, $V_{pcc}$ and FFDSOGI-PLL filtered PCC voltages. It shows that the proposed method precisely extracts the positive sequence component of PCC voltages. This can be used for generating a reference compensator current.

Fig. 9 shows the waveforms of the magnitude of fundamental active components of 3-phase load currents $(m_{a},\,\,m_{b},\,\,m_{c})$, and Fig. 10(a) shows the waveform of the fundamental current magnitude related to the requirement of total real power, $m_{f}$. Fig. 10(b) shows the waveform of unit templates of PCC voltages $u_{abc}$, which have unity magnitude and a phase displacement of 120$^{\mathrm{o}}$from each other. Fig. 10(c) shows the waveform of fundamental reference supply currents $i_{Sabc}^{*}$, which are the product of $m_{f}$ and $u_{abc}$.

Fig. 11 shows the waveform of the DC-link voltage $V_{dc}$ of VSI in the FFDSOGI-PLL-based DSTATCOM. It shows that the DC-link voltage is maintained about its reference $V_{dc}^{\mathrm{*}}$ using the PI controller.

Fig. 12 shows the waveform of the phase "a" load current $i_{La}$ and its THD. Since the load is unbalanced and nonlinear, the load current THD is increased about 18.78\%.

Figs. 13 and 14 show the waveforms of the phase "a" source current $i_{Sa}$ and PCC voltage $V_{PCCa}$ with their THD values. It shows that the FFDSOGI-PLL-based DSTATCOM compensates for the imbalance and nonlinearity of the load current and maintains THD less than 5\% according to IEEE standards.

Fig. 15 shows the waveforms of source voltage $V_{Sa}$ and source current $i_{Sa}$ of phase "a". It shows that $V_{Sa}$ and $i_{Sa}$ are in phase and that the proposed compensation technique improves the power factor to unity.

Table 1. System Parameters.

Parameters

Values

Grid supply

3-phase, 440 V(L-L), 50Hz

Ripple filter

$R_{f}$= 6${\Omega}$, $C_{f}$= 47${\mu}$F

Unbalanced linear load

$Z_{La}$= 5.5${\Omega}$+j15.7${\Omega}$

$Z_{Lb}$= 7${\Omega}$+j18.85${\Omega}$

$Z_{La}$= 8${\Omega}$+j22${\Omega}$

Nonlinear load

3-phase diode bridge rectifier fed RL load

$R$= 25${\Omega}$, $L$= 100mH

System impedance

$R_{s}$= 0.2${\Omega}$, $L_{s}$= 1mH

DC link capacitor

$C_{1}$= 1600${\mu}$F, $C_{2}$= 1600${\mu}$F

DC-link voltage reference

$V_{dc}^{\mathrm{*}}$= 1200V

Interfacing inductor

$L_{f}$= 10mH

DC PI controller gain values

$K_{P}$= 0.8, $K_{I}$= 0.4,

Hysteresis band

$\pm 0.1$ A

Fig. 7. System currents: (a) load current, $\mathbf{i}_{\mathbf{Labc}}$; (b) compensator current, $\mathbf{i}_{\mathbf{fabc}}$; (c) source current, $\mathbf{i}_{\mathbf{Sabc}}$.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig7.png
Fig. 8. System voltages: (a) PCC voltages, $\mathbf{V}_{\mathbf{pcc}}$; (b) FFDSOGI-PLL filtered PCC voltages for reference current generation.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig8.png
Fig. 9. Magnitude of fundamental active components of 3-phase load currents $(\mathbf{m}_{\mathbf{a}},\,\,\mathbf{m}_{\mathbf{b}},\,\,\mathbf{m}_{\mathbf{c}})$.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig9.png
Fig. 10. Compensator internal state variables: (a) Fundamental current magnitude, $\mathbf{m}_{\mathbf{f}}\,;$ (b) Unit templates of PCC voltages,$\mathbf{u}_{\mathbf{abc}}\,;$ (c) Fundamental reference supply currents, $\mathbf{i}_{\mathbf{Sabc}}^{*}$.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig10.png
Fig. 11. DC-link Voltage, $\mathbf{V}_{\mathbf{dc}}$.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig11.png
Fig. 12. Phase "a" Load current $\mathbf{i}_{\mathbf{La}}$ and its THD.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig12.png
Fig. 13. Phase "a" source current $\mathbf{i}_{\mathbf{Sa}}$ and its THD.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig13.png
Fig. 14. Phase "a" PCC voltage $\mathbf{V}_{\mathbf{PCCa}}$ and its THD.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig14.png
Fig. 15. Phase difference between source voltage $\mathbf{V}_{\mathbf{Sa}}$ and source current $\mathbf{i}_{\mathbf{Sa}}$ of phase "a".
../../Resources/ieie/IEIESPC.2022.11.5.376/fig15.png

6.2 Dynamic Performance Analysis

Fig. 16 shows the waveforms of various system parameters under a dynamic condition of imbalance due to the phase "b" load of the system being disconnected from t=1.1s to 1.4s.The phase "b" load current is zero from t=1.1s to 1.4s. The DSTATCOM adjusts its compensator current in a way that the source currents are sinusoidal and balanced even under dynamic conditions. Both the phase "b" fundamental active component $m_{b}$ and average component $m_{avg}$ magnitude are reduced under this dynamic condition. The DC link voltage $V_{dc}$ also slightly varies, but PCC voltages are not varied much due to these dynamics. Hence, it is observed that the proposed controller works efficiently under both steady-state and dynamic conditions.

Fig. 16. Dynamic performance of the system for the imbalance from t=1.1 s to 1.4 s.
../../Resources/ieie/IEIESPC.2022.11.5.376/fig16.png

7. Conclusion

The performance of the proposed FFDSOGI-PLL-based control technique has been illustrated for DSTATCOM to compensate for unbalanced linear and nonlinear loads in a TPFW distribution network with a weak grid. The proposed FFDSOGI-PLL was developed efficiently to estimate both the symmetrical components and phase angle of supply voltages even under a polluted grid environment. The proposed control algorithm’s performance in harmonic reduction, PFC, and load balancing, etc., was validated through various simulations in MATLAB/SIMULINK under both steady-state and dynamic conditions. Also, the source current THD was reduced to 4.97\% according to the IEEE-519 standard by the effective compensation technique.

REFERENCES

1 
Sørensen P., Unnikrishnan A., Mathew S., 2001, Wind farms connected to weak grids in India, Wind Energy, Vol. 4, No. 3, pp. 137-149DOI
2 
Kumar V., Pandey A., 2016, Grid integration and power quality issues of wind and solar energy system: A review, 2016 International Conference on Emerging Trends in Electrical Electronics & Sustainable Energy Systems (ICETEESES)DOI
3 
Adib A., Mirafzal B., Wang X., Blaabjerg F., 2018, On Stability of Voltage Source Inverters in Weak Grids, IEEE Access, Vol. 6, pp. 4427-4439DOI
4 
Singh B., Solanki J., 2009, A Comparison of Control Algorithms for DSTATCOM, IEEE Transactions on Industrial Electronics, Vol. 56, No. 7, pp. 2738-2745DOI
5 
Herrera R., SalmerÓn P., Kim H., 2008, Instantaneous Reactive Power Theory Applied to Active Power Filter Compensation: Different Approaches, Assessment, and Experimental Results, IEEE Transactions on Industrial Electronics, Vol. 55, No. 1, pp. 184-196DOI
6 
Rao U., Mishra M., Ghosh A., 2008, Control Strategies for Load Compensation Using Instantaneous Symmetrical Component Theory Under Different Supply Voltages, IEEE Transactions on Power Delivery, Vol. 23, No. 4, pp. 2310-2317URL
7 
Agarwal R., Hussain I., Singh B., 2018, Application of LMS-Based NN Structure for Power Quality Enhancement in a Distribution Network Under Abnormal Conditions, IEEE Transactions on Neural Networks and Learning Systems, Vol. 29, No. 5, pp. 1598-1607DOI
8 
Srinivas M., Hussain I., Singh B., 2016, Combined LMS-LMF-Based Control Algorithm of DSTATCOM for Power Quality Enhancement in Distribution System, IEEE Transactions on Industrial Electronics, Vol. 63, No. 7, pp. 4160-4168DOI
9 
Golestan S., Guerrero J., Vasquez J., 2017, Three-Phase PLLs: A Review of Recent Advances, IEEE Transactions on Power Electronics, Vol. 32, No. 3, pp. 1894-1907DOI
10 
Golestan S., Ramezani M., Guerrero J., Monfared F. Freijedo and M., 2014, Moving Average Filter Based Phase-Locked Loops: Performance Analysis and Design Guidelines, IEEE Transactions on Power Electronics, Vol. 29, No. 6, pp. 2750-2763DOI
11 
Xiao P., Corzine K., Venayagamoorthy G., 2008, Multiple Reference Frame-Based Control of Three-Phase PWM Boost Rectifiers under Unbalanced and Distorted Input Conditions, IEEE Transactions on Power Electronics, Vol. 23, No. 4, pp. 2006-2017DOI
12 
Li W., Ruan X., Bao C., Pan D., Wang X., 2014, Grid Synchronization Systems of Three-Phase Grid-Connected Power Converters: A Complex-Vector-Filter Perspective, IEEE Transactions on Industrial Electronics, Vol. 61, No. 4, pp. 1855-1870DOI
13 
Chittora P., Singh A. and M., 2018, Simple and efficient control of DSTATCOM in three-phase four-wire polluted grid system using MCCF-SOGI based controller, IET Generation, Transmission & Distribution, Vol. 12, No. 5, pp. 1213-1222DOI
14 
Ciobotaru M., Teodorescu R., 2006, A New Single-Phase PLL Structure Based on Second Order Generalized Integrator, 37th IEEE Power Electronics Specialists ConferenceDOI
15 
Rodríguez P., Luna A., Muñoz-Aguilar R., Etxeberria-Otadui I., Teodorescu R., Blaabjerg F., 2012, A Stationary Reference Frame Grid Synchronization System for Three-Phase Grid-Connected Power Converters Under Adverse Grid Conditions, IEEE Transactions on Power Electronics, Vol. 27, No. 1, pp. 99-112DOI
16 
Hoepfner B., Vick R., 2019, Symmetrical Components Detection With FFDSOGI-PLL Under Distorted Grid Conditions, 2019 International Conference on Smart Energy Systems and Technologies (SEST)DOI
17 
Nagarajan C., Madheswaran M., 2010, Performance Estimation of LCL-T Resonant Converter with Fuzzy/ PID Controller Using State Space Analysis, International Journal of Computer and Electrical Engineering, pp. 534-542DOI
18 
Nagarajan C., Madheswaran M., 2011, Stability Analysis of Series Parallel Resonant Converter with Fuzzy Logic Controller Using State Space Techniques, Electric Power Components and Systems, Vol. 39, No. 8, pp. 780-793DOI

Author

Balasubramanian M
../../Resources/ieie/IEIESPC.2022.11.5.376/au1.png

Balasubramanian M received a BE degree in electrical and electronics engineering in 2006 and an ME degree (power systems) in 2009 from Anna University, Chennai, India. He is currently working as an assistant professor in Government College of Engineering, Tirunelveli, Tamilnadu, India. His area of interest includes active power filters, power quality improvement in distribution systems, and renewable energy systems. He is a lifetime member of ISTE and IEI, India.

Nagarajan C
../../Resources/ieie/IEIESPC.2022.11.5.376/au2.png

Nagarajan C received a BE degree from K.S. Rangasamy College of Technology, India, which is affiliated with Madras University, in 1997-2001 and an M. Tech. degree from the Vellore Institute of Technology, Vellore, Tamilnadu, India, in 2004. He obtained a PhD degree in electrical engineering from BIHER University, Chennai, India. At present, he is a professor in the EEE department at Muthayammal College of Engineering, Rasipuram, India. He has authored over 85 research publications in international and national journals and conferences. He guided 10 research PhD scholars in Anna University, and 6 scholars are doing research under his guidelines. He published two patents. He has been a member of the faculty at the Centre for Advanced Research, Muthayammal Engineering College, Rasipuram, Tamilnadu, India, since 2005. His research interests include fuzzy logic and neural network applications for power electronics and drives. He is a lifetime member of IETE, ISTE, and IE (India) and also a member of IEEE.