Mobile QR Code QR CODE : Journal of the Korean Society of Civil Engineers
Title Structural Performance Evaluation of Anchors for Power Equipment Electrical Cabinets Considering On-Site Installation Conditions
Authors 이상문(Lee, Sang-Moon) ; 정우영(Jung, Woo-Young)
DOI https://doi.org/10.12652/Ksce.2023.43.6.0709
Page pp.709-719
ISSN 10156348
Keywords 후설치 앵커; 정적 성능 평가; 앵커 인발; 3D FEM; ABAQUS Post-installed anchor; Static performance testing; Anchor pull-out; 3D FEM; ABAQUS
Abstract In general, most of the electrical equipment responsible for control within power plants is housed in self-standing cabinets. These cabinets are typically fixed to a slab using post-installed anchors. Although the fixation method of using post-installed anchors provides stability, there is a risk of conductor failure due to external forces, including moments. However, the performance assessment of current anchors is only evaluated through uniaxial material tests. Therefore, the primary purpose of this study is to compare the static performance of post-installed anchors, considering on-site installation conditions, with their performance in material tests and to analyze the behavioral characteristics of the anchors. While conducting experiments using actual cabinets would be ideal, practical and spatial constraints make this approach difficult. As an alternative, experiments were conducted using a test specimen consisting of a steel column and a support. As a result, the pull-out performance of anchors reflecting on-site installation conditions was measured to be about 10% higher than that observed in material tests. The trends in load reduction and the point of maximum performance for the anchors also differed. To verify the reliability of the experimental study, a 3D FEM analysis was performed, which will provide predictive information on the loads transferred to the post-installed anchors for structural performance evaluations of electrical cabinets using shaking table test in the future.