Title 24 Pulse Current Source Inverter For Reducing the Harmonics in Output Currents
Authors 유철로 ; 이공희 ; 이성룡 ; 한우용
Page pp.24-31
ISSN 1975-8359
Keywords 24펼스 전류원 인버어터 ; 고조파저감 24 Pulse Current Source Inverter ; Reducing Harmonics
Abstract A 24 pulse current source inverter for reducing the harmonics in output currents is presented in this paper. The proposed system operates a 24 pulse inverter by adding only tap changing circuit which consists of several taps and static switching elements to the 12 pulse inverter, which is the double connected 3 phase 6 pulse inverter with an auto transfomer. Also to optimize the effectiveness of the harmonic reduction, the optimum turn ratio and tap changing control angle of auto transfomer are decided by digital simulation and its validity is verified with experiment. And under the optimum condition, it is clarified that the harmonics components involved in the output current of the proposed inverter are nearly equal to those of the conventional 24 pulse inverter.