Title A Study on Parallel Operation Between Inverter System and Utility Line
Authors 천희영 ; 박귀태 ; 유지윤 ; 안호균
Page pp.369-378
ISSN 1975-8359
Keywords 독립현 인버터 ; 병령형인버터 stand-alone inverter ; parallel processing inverter
Abstract This paper proposes a utility parallel processing inverter system, which consists of a voltage source PWM inverter, isolation transformer and a reactor linking the inverter to utility line. This system realizes following functions : (1) voltage phase frequency and amplitude synchronization between inverter and utility line at stand-alone mode. (2) current phase synchronization between inverter and load at parallel mode. Therefore, despite sudden increase in load current over setting point at stand-alone mode, inverter system can be transferred into parallel mode immediately without transient current. Furthermore, high frequency(18KHz) PWM control and sinusoidal filtering improve the inverter output waveform by eliminating high order harmonic components as well as low order. As a switching device, IGBT is used for high frequency switching and large current capacity.