Title Development of a Deterioration Diagnostic Device for ZnO Arrester by Leakage Current Detection
Authors 김재철(Kim, Jae-Chul) ; 이보호(Lee, Bo-Ho) ; 오정환(Oh, Jung-Hwan) ; 이영길(Lee, Young-Gil) ; 문선호(Moon, Sun-Ho) ; 김영춘(Kim, Young-Chun)
Page pp.184-189
ISSN 1975-8359
Keywords ZnO arrester ; Leakage current ; Resistive current ; The third harmonic current
Abstract In this paper, we develope a diagnosis device for ZnO arrester by detecting the leakage current in service. To diagnose the deterioration of ZnO arrester, the device detects the total leakage current which flows between an arrester and ground, and analyzes the resistive current(third harmonic current) which is an indicator of deterioration of ZnO arrester. We use the optical cable which can transfer a detected data without a noise, also use a microprocessor for a data storage, processing, and trend analysis. Experiment are executed to verify its performance in laboratory and the results show that the diagnosis device exactly detects the total leakage current and the resistive current, so it can diagnose the deterioration of ZnO arrester. Also the leakage current of ZnO arrester is detected using the developed diagnostic device in field, these results are presented.