• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Analysis of Sheath Induced Voltage in Transmission Power Cable Connected with CCPU
Authors 이준성(Lee, Jun-Sung) ; 이종범(Lee, Jong-Beom) ; 김영(Kim ,Young)
Page pp.19-25
ISSN 1975-8359
Keywords Sheath Induced Voltage ; CCPU ; Cross-Bond Grounding ; Grounding Method ; EMTP ; ATP Draw
Abstract This paper describes the sheath induced voltage in underground transmission cable system which will be operated with cable cover protection unit(CCPU). Simulation was carried out to analyze the sheath induced voltage in the real cable system which was installed by 154㎸ CV cable in the case with and without CCPU. The sheath induced voltage will be also analyzed according to the change of grounding method, fault resistance and fault angle. Simulation was performed using EMTP and ATP Draw, the simulation results show whether the CCPU in necessary or not in underground transmission power cable system.