Title The DC Link Energy Control Method of Dynamic Voltage Restorer System
Authors 정일엽(Jeong, Il-Yeop) ; 박상영(Park, Sang-Yeong) ; 원동준(Won, Dong-Jun) ; 문승일(Mun, Seung-Il) ; 박종근(Park, Jong-Geun) ; 한병문(Han, Byeong-Mun)
Page pp.575-583
ISSN 1975-8359
Keywords Dynamic Voltage Restorer (DVR) ; DC Link Energy ; Custom Power ; Power Quality
Abstract Dynamic Voltage Restorer(DVR) which is installed between the supply and a critical load can restore voltage disturbances in distribution system. The restoration is based on injecting the same voltages as voltage sags. The ideal restoration is compensation to make the load voltages be unchanged. But voltage restoration involves real power or energy injection and the capability of energy storage is limited. So it must be considered how injection energy can be minimized and voltages can be made close to the voltages before fault. This paper describes conventional restoration techniques, which draw minimum energy from the DVR in order to correct a given voltage sag or swell. And this paper proposes a new concept of restoration technique to inject minimum energy. The proposed method is based on the definition of voltage tolerance in load side. Hence using the proposed method a particular disturbance can be corrected with less amount of storage energy compared to those of conventional methods.