• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title A New fault Location Algorithm for a Line to Ground fault Using Direct 3-phase Circuit Analysis in Distribution Power Networks
Authors 최면송(Choe, Myeon-Song) ; 이승재(Lee, Seung-Jae) ; 이덕수(Lee, Deok-Su) ; 진보건(Jin, Bo-Geon) ; 민병운(Min, Byeong-Un)
Page pp.409-416
ISSN 1975-8359
Keywords Fault Location ; Direct 3-Phase Circuit Analysis ; Distribution Power Systems
Abstract This paper presents a fault location algorithm using direct 3-phase circuit analysis for distribution power networks. The unbalanced feature of distribution networks due to single phase loads or asymmetric operation prohibits us from using the conventional symmetrical component transformation. Even though the symmetrical component transformation provides us with a very easy tool in three phase network analysis, it is limited to balanced systems in utilizing its strong point, which is not suitable for distribution networks. In this paper, a fault location algorithm using direct 3-phase circuit analysis is developed. The algorithm is derived and it Is shown that the proposed method if we use matrix inverse lemma, is not more difficult then the conventional methods using symmetrical component transformation. Since the symmetrical component transformation is not used in the suggested method, unbalanced networks also can be handled with the same difficulty as balanced networks. The case study results show the correctness and effectiveness of the proposed algorithm.