• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Analysis of Sheath Circulating Current on Multi-underground Transmission Cables using EMTP
Authors 하체웅(Ha, Che-Ung) ; 김정년(Kim, Jeong-Nyeon) ; 이수길(Lee, Su-Gil) ; 김동욱(Kim, Dong-Uk) ; 이종범(Lee, Jong-Beom) ; 강지원(Gang, Ji-Won)
Page pp.510-517
ISSN 1975-8359
Keywords Sheath circulating current ; Cross-bonded section ; EMTP ; impedance reduction system
Abstract The use of underground transmission cables has continuously increased in densely inhabited urban and suburban area. Due to a increasing demand of underground cables, two or more circuits are installed in parallel for several kilometers. It, however, has not been realized that the sheath circulating current is generated in the system where a large number of cables are laid in the same route. In this paper, sheath circulating current is analyzed by the EMTP and compared with the measured values. Unbalance arrangement of cables or cross-bonding length causes a significant effect on the magnitude of the sheath current. Sheath circulating current could be greatly reduced by the symmetrical configuration of cables and installation of the impedance reduction system. Especially, with the impedance system of 1Ω installed, the sheath circulating current is reduced by 85.7%.