Title A Study on the Characteristic and Rising Cause of Sheath Circulating Current by Analysis and Measurement
Authors 강지원(Gang, Ji-Won) ; 양해원(Yang, Hae-Won)
Page pp.525-533
ISSN 1975-8359
Keywords Underground transmission system ; Sheath circulating current ; Distribution cable ; EMTP/ATPDraw
Abstract It is common to install multiple lines in the same route. Recently, excessive sheath circulating current was partially measured in underground cable systems of KEPCO. Especially, the installation type, unbalance section length between joint boxes and zero sequence current by distribution cable have an effect on the rising of sheath circulating current in the underground transmission system. If excessive current flows in sheath, sheath loss which is reduced the transmission capacity is produced. This paper describes the relation analysis of sheath circulating current and burying types. And also, a detailed analysis on rising cause and characteristic of sheath circulating current by considering various unbalanced conditions presents using analysis and measurement regarding cable systems which have the problem of excessive sheath circulation current.