Title A Study for the Voltage Analysis Method of Distribution Systems with Distributed Generation
Authors 김태응 ; 김재언
Page pp.69-78
ISSN 1975-8359
Keywords Distribution System Modeling ; DG(Distributed Generation) ; ULTC(Under Load Tap Changer) ; Voltage Analysis Method
Abstract This paper presents a voltage analysis method of distribution systems interconnected with DG(Distributed Generation). Nowadays, small scale DG becomes to be introduced into power distribution systems. But in that case, it is difficult to properly maintain the terminal voltage of low voltage customers by using only ULTC(Under Load Tap Changer). This paper presents a voltage analysis method of distribution systems with DC for proper voltage regulation of power distribution systems with ULTC. In order to develop the voltage analysis method, distribution system modeling method and advanced loadflow method are proposed. Proposed method has been applied to a 22.9 kV practical power distribution systems.