Title Insulation Design Standards for Protection of Power System against Lightning in Korea Electric Power Corporation
Authors 우정욱(Woo, J.W.) ; 문재덕(Moon, J.D.)
Page pp.555-560
ISSN 1975-8359
Keywords Insulation Coordination ; Standard Design ; Lightning ; Flashover ; Lighting Performance ; Transmission Line
Abstract As it has been reported that more than 60% of transmission line faults occurs due to lightning strokes, lighting is one of concerned issues in electric power utility company. Most of transmission line is double circuit in Korea. Double circuit outages account for 33.7 percent of total lightning faults from 1996 to 2004. Even though transmission fault might be cleared shortly by protective system, it could deteriorate the power quality accompanied with sag or flicker. Moreover, double circuit fault may lead to more aggravated situation, for instance, blackout. To Protect transmission lines from lightning stroke, reduction of tower footing resistance, multiple ground wires and unbalanced insulation in double circuit lines have been adopted. In this paper, we would like to introduce insulation design standards for lightning protection of Korea Electric Power Corporation.