• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title An EMTDC Analysis for Ground Faults with a Superconducting Fault Current Limiter
Authors 최효상(Choe, Hyo-Sang) ; 현옥배(Hyeon, Ok-Bae) ; 고태국(Go, Tae-Guk)
Page pp.161-166
ISSN 1975-8359
Keywords Superconducting Fault Current Limiter ; EMTDC Simulation ; Ground Fault ; Circuit Breaker
Abstract We have performed an EMTDC simulation for the current limiting effects of a superconducting fault current limiter (SFCL). The fault currents in the 154 kV transmission line between the arbitrary S1 and S2 substations increased up to 39 kA during the single and double line-to-ground faults, respectively. The SFCL in the transmission line is sufficient.