Title The Phenomena Giving Rise of Nonlinear Load Operated by Unbalance Voltage
Authors 김종겸(Kim, Jong-Gyeom) ; 이은웅(Lee, Eun-Ung)
Page pp.285-291
ISSN 1975-8359
Keywords Voltage Unbalance ; Current Unbalance ; nonlinear-Load ; Harmonics ; ASD ; THD
Abstract In general, utility voltage is maintained at a relatively low level of Phase unbalance since a low level of unbalance can cause a significant power supply ripple and heating effects on the power system equipment. Voltage unbalance more commonly emerges in individual customer loads due to phase load unbalanced, especially where single phase power loads are used. Under unbalanced input voltages large lower order harmonics appears at the input and output ports of Power conversion devices. As the application of adjustable -speed drives (ASDs) and their integration with complex industrial processes increase, so does the need to understand how ASDs perform during voltage This paper describes a real load test to investigate the performance of 3-HP adjustable speed drives by an unbalanced voltage at the low-voltage system.