Title Test Results of a Three Phase 10㎸A HTS Transformer With Double Pan Cake Coils
Authors 이승욱 ; 이희준 ; 차귀수 ; 이지광 ; 최경달 ; 류경우 ; 한송엽
Page pp.101-106
ISSN 1975-8359
Keywords HTS transformer ; double pancake winding ; Continuous operation ; liquid nitrogen auto filling
Abstract The high temperature superconductor transformers gain interests from the industries. This paper described construction and test results of 10㎸A HTS transformer Three phase transformer with double pancake windings were constructed. To reduce the leakage magnetic field, secondary coil were placed between the two primary coils. BSCCO-2223 wire. silicon sheet steel core and FRP cryostats were used to construct the transformer. Three coils were stacked in one cryostat. Two double pancake coils were connected in series for the primary coil and one double pancake coil was used for the secondary coil. Total number of turns of the primary winding and the secondary winding were 112turns and 98urns, respectively, The rated voltages of each winding were 440/220V. The rated currents of each winding were 13.1/26.2A. After the tests of basic properties of the three phase HTS transformer using no-load test, short-circuit test and full-load test, continuous operation of 100 hours with pure resistive load has been carried out. Test results proved over-load capability and reliability of the HTS transformer.