• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title The Consideration of Electrical Characteristics and Breakdown Lifetime in 22.9[kV] Underground Distribution Power Cables
Authors 김충배(Kim, Chung-Bae) ; 홍경진(Hong, Gyeong-Jin) ; 임장섭(Im, Jang-Seop) ; 정우성(Jeong, U-Seong) ; 김상준(Kim, Sang-Jun) ; 김태성(Kim, Tae-Seong)
Page pp.628-633
ISSN 1975-8359
Keywords Power cable ; Degradation diagnosis ; Weibull distribution function ; Breakdown lifetime
Abstract Degradation diagnosis of XLPE insulated URD cables was accomplished through out new method, which was to be analyzed by non-electrical experiments and synthesized by degradation points. To supplement this method, It was also carried out using several electrical analyses. TanΔ had commonly a different tendency by means oftemperature and frequency and also appeared higher at the outer part rather than innerpart of insulator. PD-q increased generally in proportion to the applied voltage andshowed regular patterns in relation to the thickness of insulator. Breakdown voltageswere measured and breakdown lifetimes were predicted appling for Weibull distribution function. As a result, breakdown lifetime in failure cables was shorter up to fraction one-third times than that in general cables. It was very available to estimate cable degradation using above method, but it needs further study on XLPE insulated URD cables in order to improve reliability.