• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Risk Assessment on Free Conducting Particle in GIS
Authors 윤진열(Yun, Jin-Yeol) ; 박기준(Park, Gi-Jun) ; 구선근(Gu, Seon-Geun)
Page pp.164-168
ISSN 1975-8359
Keywords GIS ; particle ; bouncing height ; risk assessment ; breakdown
Abstract The main hazard leading to breakdown in GIS(Gas Insulated Switchgear) comes from free conducting particles, which can cross between tee electrodes and cause dielectric failure under the influence of the electric field. Bouncing height of the particle can be an important factor to evaluate the possibility of breakdown occurrence. In this paper, how to estimate, outside a GIS, the bouncing height of the particle was newly suggested when GIS is in service. Both experimental results using 362 kV test chamber and computer simulation results on estimating the height were presented and compared with each other.