Title Partial Discharge Phenomena with SF_{6} Gas Pressures in Insulation Consisted of Insulation Paper and SF_{6} Gas(II)
Authors 선종호(Seon, Jong-Ho) ; 김광화(Kim, Gwang-Hwa) ; 박정후(Park, Jeong-Hu) ; 조정수(Jo, Jeong-Su)
Page pp.430-435
ISSN 1975-8359
Keywords Partial Discharge ; Paschen′s Law ; SF_{6} Gas Gap ; Aramid Paper
Abstract The SF_{6} gas insulated power equipments have the insulation systems which are composed of SF_{6} gas and insulation paper. It is repored that their insulation abilities are influenced by the SF_{6} gas gaps in those insulation systems and gas pressures. This paper describes partial discharge phenomena with SF_{6} gas pressures in insulation system of SF_{6} gas-insulation paper Specimens of SF_{6} gas-insulation paper were prepared and aramid paper was used as insulation paper. Partial discharge inception voltages(PDIV) and breakdown voltages for the existence of SF_{6} gas gaps were measured by short term tests with gas pressures. Also, average PD quantities and pulse counts, life times of each specimens were calculated from the results of long term aging tests with gas pressures. It was found that the SF_{6} gas gaps decrease increasing rates of PDIV and brealdown voltages according to gas pressure increase and the insulation breakdown caused by the smaller PD quantities than 1[pC] at the high gas pressure of 300kPa is due to the increase of energy density with increase of gas pressure.