• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Influence of Harmonics in Power System Voltage on Arrester Deterioration Diagnostics by Leakage Current Measurement
Authors 길경석 ; 한주섭 ; 주문노
Page pp.42-46
ISSN 1975-8359
Keywords arrester ; leakage current deterioration harmonics ; diagnostic techniques ; ZnO arrester model ; power system voltage
Abstract Arresters are deteriorated by overvoltages or impulse currents, and the resistive leakage current of arresters increases as the deterioration of the arrester progresses, showing an increase in the 3^{rd} harmonic component of the leakage current. In this reason, arrester diagnostic techniques based on the 3^{rd} harmonic leakage current as a reference parameter of deterioration are widely used. The technique, however, includes an error due to the harmonics of power system voltage. Therefore, the influence of the harmonics on arrester diagnostics should be considered. In this paper, we designed a PSpice ZnO arrester model to simulate the influence of the voltage harmonics described above. A pure sinusoidal voltage and its the 3r harmonic voltage were applied to the model, and the leakage current components were analyzed. From the simulation results, it is confirmed that the peak value of resistive leakage current depends not only on the phase of the 3^{rd} harmonic voltage but also on the magnitude of it. Consequently, the errors caused 1)y the harmonic voltage could be minimized by correcting the magnitude of leakage current upon analyzing the harmonics.cs.