• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title A Study on the Influence of Harmonics in Power System Voltage on Arrester Diagnostics and its Compensation
Authors 김일권(Kim, Il-Kwon) ; 송재용(Song, Jae-Yong) ; 한주섭(Han, Ju-Seop) ; 길경석(Kil, Gyung-Suk) ; 류길수(Rhyu, Keel-Soo) ; 조한구(Cho, Han-Goo)
Page pp.493-497
ISSN 1975-8359
Keywords ZnO Arrester ; Leakage Current ; Deterioration ; Harmonics ; Diagnostic Techniques ; Power System Voltage
Abstract This paper dealt with the influence of harmonic voltages on arrester diagnostics and its compensation method by using a designed Pspice arrester model. A pure sinusoidal voltage and its 3^{rd} harmonic voltage were applied to the model, and the leakage current components were analyzed. The simulation results have shown that the peak value of resistive leakage current depends not only on the phase of the 3^{rd} harmonic voltage but also on the magnitude of it. In this paper, an approximated 5^{th} order polynomial formula by the Least-Square-Technique was derived, and correction factors which compensate the error caused by the 3^{rd} harmonic voltage were calculated.