• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title On-Site Calibration Technology of Burden using Voltage Transformer Comparator
Authors 정재갑(Jung, Jae Kap) ; 권성원(Kwon, Sung Won) ; 박영태(Park, Young Tae) ; 김명수(Kim, Myung Soo)
Page pp.503-507
ISSN 1975-8359
Keywords Voltage Transformer ; Ratio Error ; Phase Angle Error ; Burden Value ; Power Factor ; Voltage Transformer Comparator
Abstract Both ratio error and phase angle error in voltage transformer(VT) depend on values of VT burden used. Thus, precise measurement of burden is very important for the evaluation of VT. A method of evaluation for VT burden has been developed by employing the portable decade resistor, with AC-DC resistance difference less than 10-3. The burden value(value and power factor) can be obtained by conductance and susceptance, obtained by measuring the change of ratio error and phase angle error caused by the resistance change of decade resistor. The burden value and power factor obtained by the method are consistent with those obtained using power analyzer within corresponding uncertainties.