Title Properties of On-Line Partial Discharge in Hydrogenerator Stator Windings
Authors 김병한(Kim, Byong-Han) ; 김희동(Kim, Hee-Dong)
Page pp.172-177
ISSN 1975-8359
Keywords Partial Discharge ; Hydrogenerator ; Normalized Quantity Number ; PD Magnitude ; Stator Winding
Abstract During normal machine operation, partial discharge(PD) tests were performed with partial discharge analyzer(PDA) in two hydrogenerators. Six cable couplers were installed in circuit ring bus and endwinding of three phases. PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude(Q_m) were very low in hydrogenerator #1 and #2, respectively. The trend analyses of NQN and Q_m value are available for monitoring of the insulation condition in hydrogenerator stator windings. The insulation condition of stator winding can be assessed. Discharge at conductor surface was discovered in B phase(C2 coupler) of hydrogenerator #1. Internal discharges were generated in A and C phases(C2 coupler) of hydrogenerator #1 and in A, Band C phases(C1 and C2 couplers) of hydrogenerator #2. Slot discharges occurred in A, Band C phases(C1 coupler) of hydrogenerator #1. The stator windings of two hydrogenerators were in good condition.