Title An Improved Method of Faulted Section Identification Algorithm in Distribution Automation System
Authors 임일형(Lim, Il-Hyung) ; 임성일(Lim, Seong-Il) ; 이승재(Lee, Seung-Jae) ; 권성철(Kwon, Sung-Chul) ; 신창훈(Shin, Chang-Hoon) ; 하복남(Ha, Bok-Nam) ; 최면송(Choi, Myeon-Song)
Page pp.651-659
ISSN 1975-8359
Keywords 배전자동화 ; 고장표시 ; 고장전류 Fault Indicator ; FI ; FRTU
Abstract This paper proposes an improved fault indication algorithm in a distribution automation system. A conventional fault indication method, so called YES-NO algorithm, could generate wrong informations under certain conditions such as line to ground fault, large motor double circuit line. In order to prevent mal-operation of fault indicator, direction of fault current are used as well as magnitude. The feasibility of the proposed algorithm has been testified by computer simulation using Matlab power system toolbox.