Title Construction of On-Site Calibration Facilities of 66 kV Voltage Transformer Comparator System
Authors 정재갑(Jung, Jae-Kap) ; 이상화(Lee, Sang-Hwa) ; 권성원(Kwon, Sung-Won) ; 김명수(Kim, Myung-Soo)
Page pp.1268-1274
ISSN 1975-8359
Keywords Voltage transformer ; Voltage transformer comparator ; Traveling standard ; Ratio error ; Phase angle error ; Burden ; Linearity
Abstract A recently developed methods for the on-site calibration of the voltage transformer (VT) comparator system have been reviewed in the paper. The method utilizes the several traveling standards consisting of the VT, the non-reactive standard resistors, the wide ratio error VT, and the decade resistors. The VT is used for the absolute evaluation of a standard VT belonging to the industry. The non-reactive standard resistor and wide ratio error VT are used for the linearity check of errors in the voltage comparator of the industry. The decade resistors are used for evaluation of a VT burden of the industry.