• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Study on the Measurement of Radiation Energy of the Arc in GCBs
Authors 송기동(Song, Ki-Dong) ; 오연호(Oh, Yeon-Ho) ; 정진교(Chong, Jin-Kyo) ; 조용성(Cho, Young-Sung)
Page pp.2122-2126
ISSN 1975-8359
Keywords PM-Tube ; Radiation ; Arc ; SF_6 gas ; GCB
Abstract A special PM-Tube(Photo Multiplier Tube) that is using the photoelectric effect has been designed and manufactured to measure the radiation energy of arc in a gas circuit breaker(GCB). The PM-Tube, LLG(liquid light guides), ND(neutral density) filter, and a model gas circuit breaker have been combined for the reception and the transmission of the light and a simplified synthetic test facility with the arc energy measuring system has been established. In the case of SF_6 gas pressure 5kg.f/cm^2 and arc length 20mm, the radiation energy increases with the arc current but it tend to be saturated in the above 20kA. Under the arc current 20kA, the total radiation energy has the biggest value around 8kA and was not exceeded 40% of the total arc energy.