Title Partial Discharge Location Method using Group Velocity Difference of Modes in a Electromagnetic Partial Discharge Signal in Gas Insulated Bus
Authors 구선근(Goo, Sun-Geun) ; 주형준(Ju, Hyoung-Jun) ; 박기준(Park, Ki-Jun) ; 한기선(Han, Ki-Seon) ; 윤진열(Yoon, Jin-Yul)
Page pp.2184-2188
ISSN 1975-8359
Keywords Partial Discharge ; Gas Insulated Bus ; Location ; Mode ; Group Velocity
Abstract We developed a novel method of partial discharge(PD) location based on the fact that the waveform of PD signal propagate along the GIB (Gas Insulated Bus) is composed of several modes of electromagnetic wave with different group velocities and cut-off frequencies. From the PD waveform, measured at a broadband PD sensor attached on the GIB, we could derive arrival time and frequency components of different modes using the short term Fourier transform or etc. After the group velocities of different modes are calculated, the location of the PD source could be estimated. To show the effectiveness of this new locating method in a real on site application, we used this method to locate the position of a PD source at a 76 m long 345 kV GIB substation. The estimated location of the PD source using the method proposed above was in good agreement with the actual location found from the inspection result of internal component in the GIB with 2.4% of the estimation error.