Title Field Test and Analysis for Proper Location of Protective Equipment in Underground Distribution System
Authors 윤창섭(Yun, Chang-Sub) ; 이종범(Lee, Jong-Beom)
Page pp.773-782
ISSN 1975-8359
Keywords Underground Distribution System ; EMTP ; Cable ; Modeling ; Field test
Abstract This paper describes the method for proper location of protective equipment in underground distribution cable through field test and analysis at testing lines. To prove the reliability for analysis simulated by EMTP/ATPDraw, the testing results obtained by the real test and the analysis for the same test lines were compared each other. The accuracy of analysis was proved by the comparison. Over voltages were measured and analyzed at each point of cable and switches in case of which lightning surge current was applied. The analysing method was applied to real distribution systems to select the proper location of protective equipment. It is evaluated that the location of protective equipment was properly selected.