Title Calculation of an Induced Voltage on Telecommunication Lines in Parallel Distribution Lines
Authors 김현수(Kim, Hyun-Soo) ; 이상봉(Rhee, Sang-Bong) ; 여상민(Yeo, Sang-Min) ; 김철환(Kim, Chul-Hwan) ; 류승헌(Lyu, Seong-Heon) ; 김성암(Kim, Seong-Arm) ; 원봉주(Weon, Bong-Ju)
Page pp.1688-1695
ISSN 1975-8359
Keywords EMTP ; Distribution System ; Induced Voltage ; Telecommunication Line
Abstract Recently, it is common in a distribution system of Korea Electric Power Corporation (KEPCO) to find instances where distribution lines are parallel. A traditional method of an induced voltage calculation is not suitable for parallel distribution lines. For more actual analysis of induced voltage on telecommunication lines in parallel distribution lines, a new calculation method is needed. This paper presents a new calculation method of an induced voltage on telecommunication line using equivalent π circuits matrix in parallel distribution lines. The advantages of the calculation method are using actual neutral current value and not using screening factor for considering the overhead ground wire and the neutral wire. To verify the effectiveness and the accuracy of the method, various case studies are performed with EMTP(Electro-Magnetic Transients Program).