Title A Study on the Core Noise Reduction Techniques of Power Transformers
Authors 권동진(Kweon, Dong-Jin) ; 구교선(Koo, Kyo-Sun) ; 조익춘(Cho, Ik-Choon) ; 김유현(Kim, Yoo-Hyun) ; 김융식(Kim, Yung-Sig)
Page pp.1962-1969
ISSN 1975-8359
Keywords Transformer ; Core ; Noise ; Vibration ; Step lap
Abstract According to the increase of power demand and expansion of downtown, it is necessary to install transformers additionally in operating substations and construct substations in residential area. But the public complaint is increased due to the transformer noise of the substation. KEPCO has used a vibration preventing pad, various soundproof walls and an encloser to transformers in outdoor substations, and a soundproof door, shutter and wind-path soundproof equipment in indoor substations to block the sound propagation of the transformers. But these noise reduction methods are not satisfied. It should be considered to reduce transformer noise itself. In this paper, we investigated core noise reduction techniques to develope a low noise transformer. The techniques to reduce core noise of the transformer are application of high permeability grain oriented silicon sheets, decrease of magnetic flux density of core, application of 6step-lap core stacking method, improvement of core binding method(binding addition, band fixing) and application of rubber damper in oder to reduce transmission of core vibration, etc.