Title An Analysis of Superconducting Fault Current Limiter Operation According to Asymmetry Fault Current
Authors 이상봉(Rhee, Sang-Bong) ; 김철환(Kim, Chul-Hwan) ; 김규호(Kim, Kyu-Ho) ; 김재철(Kim, Jae-Chul) ; 현옥배(Hyun, Ok-Bae)
Page pp.450-454
ISSN 1975-8359
Keywords Asymmetry Current ; Electro-Magnetic Transients Program(EMTP) ; Superconducting Fault Current Limiter
Abstract This paper analyzes a asymmetry current with SFCL (Superconducting Fault Current Limiter) operation during transient period, when a fault occurs in power systems. The principle of asymmetry current nature is reviewed and asymmetry components reduction with SFCL operation is explained. To verify the performance of SFCL, a EMTP/ATPDraw model of SFCLs using MODELS language developed and simulated. Throughout the simulation, results presents the main factors for reducing the asymmetry component of fault current are not a quenching time, but a limiting resistance of SFCL and fault initiated angle.