• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Characteristics of Ultra High Frequency Partial Discharge Signals of Turn to Turn Defect in Transformer Oil
Authors 윤진열(Yoon, Jin-Yul) ; 주형준(Ju, Hyung-Jun) ; 구선근(Goo, Sun-Geun) ; 박기준(Park, Ki-Jun)
Page pp.2000-2004
ISSN 1975-8359
Keywords UHF PD Signal ; Power Transformer ; Turn to Turn Defect ; PRPD Pattern
Abstract In general, for the condition monitoring of a power transformer using the UHF PD measuring technique, detection of any partial discharge, identifying the defect in the transformer and locating the insulation defect are necessary. In this paper one of the most frequent detects which can result in turn to turn fault in power transformer was examined for identifying the defect. In order to model the defect, as a discharge source, a partial discharge cell was used for experimental activity. Magnitude of electromagnetic wave signals and corresponding amount of apparent discharge were measured simultaneously against phase of applied voltage to the discharge cell. Frequency range and phase resolved partial discharge signals were measured and analyzed. The results will be contributed to build the defect database of power transformer and to decrease the occurrence of transformer faults.