• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Analysis for Insulating Degradation Characteristics with Aging Time for Oil-filled Transformers and/or Correlation between using Linear Regression Method
Authors 이승민(Lee, Seung-Min)
Page pp.693-699
ISSN 1975-8359
Keywords Oil-filled transformer ; Tensile Strength ; HPLC ; Correlation ; Linear Regression
Abstract General transformer's life is known as paper insulation' life. If a transformer is degraded by these aging factors, it is known that electrical, mechanical and chemical characteristics for transformer's oil-paper are changed. When the kraft paper is aged, the cellulose polymer chains break down into shorter lengths. It causes decrease in both tensile strength and degree of polymerization of paper insulation. The paper breakdown is accompanied by an increase in the content of furanic compounds within the dielectric liquid. In this paper it is aimed at analysis on correlation between aging characteristics for insulating diagnosis of thermally aged paper. For investigating the accelerated aging process of oil-paper samples accelerating aging cell was manufactured for estimating variation of paper insulation during 500 hours at 140°C temperature. To derive the results, it was performed analysis such as tensile strength(TS), depolymerization(DP), dielectric strength(DS), relative permittivity, water content(WC) and furan compound(FC) for aged paper. Also for analyzing correlation between insulating degradation characteristics, we used linear regression method. As as results of linear regression analysis, there was a close correlation between TS and DP. WC, FC. But dielectric strength was a weak correlation with aging time.