• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Assessment of Insulation Condition in Gas Turbine Generator Stator Windings
Authors 김희동(Kim, Hee-Dong) ; 양규현(Yang, Gyu-Hyun) ; 주영호(Ju, Young-Ho)
Page pp.1423-1428
ISSN 1975-8359
Keywords Condition monitoring ; Diagnostics ; Generator ; Insulation testing ; Partial discharge ; Stator winding
Abstract The results of off-line and on-line diagnostic tests performed on the stator winding of an air-cooled gas turbine(G/T) generator are reported in this paper. Off-line diagnostic tests included measurements of the ac current, dissipation factor(tanδ), and partial discharge(PD). Six epoxy-mica capacitors were installed in the three phases of G/T generator for performing on-line diagnostic testing with the turbine generator analyzer(TGA). The TGA showed that the normalized quantity number(NQN) and the PD magnitude(Q_m) were high in phase A of the stator winding. Internal discharges were generated in phases B and C, and slot discharge occurred in phase A. According to the trend analyses of the NQN and Q_m values available for insulation condition assessment for G/T generator stator windings, it was concluded that phases B and C were in good condition, whereas phase A has been significantly deteriorated.