• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Review on the Relationship of Dissolved Gas Analysis and Internal Inspection of Transformer
Authors 박현주(Park, Hyun-Joo) ; 남창현(Nam, Chang-Hyun) ; 정년호(Jung, Nyun-Ho)
Page pp.1869-1873
ISSN 1975-8359
Keywords Transformer ; DGA(Dissolved Gas Analysis) ; 2-furaldehyde ; Internal inspection
Abstract For reliable operation of oil-filled electrical equipment, monitoring and maintenance of insulating oil is essential. Dissolved gas analysis(DGA) is widely used for monitoring faults in high voltage electrical equipment in service. Therefore, oil analysis should be monitored regularly during its service life. KEPCO has investigated thousands of dissolved gas analysis data since 1985, and conducted studies on the relationship of gas in oil analysis and internal inspection results of transformer. As the results, KEPCO revised criteria for transformer diagnosis and has applied it since 2008. Almost of 100 cases of internal inspection results since 2001 have been investigated. This paper presents the correlation of the fault-identifying gases with faults found in actual transformers and how should we approach to internal inspection of transformer by dissolved gas analysis.