Title Evaluation of Operation Practicality on Line with Aluminum Conductor in Underground T&D Systems
Authors 장주영(Jang, Ju-Yeong) ; 이종범(Lee, Jong-Beom) ; 김용갑(Kim, Yong-Kap)
DOI https://doi.org/10.5370/KIEE.2011.60.3.492
Page pp.492-499
ISSN 1975-8359
Keywords Cu conductor cable ; Al conductor cable ; Lightning surge ; Fault current ; Allowance current
Abstract This paper describes that the evaluation on operation practicality of Al conductor cable will be used instead of Cu conductor cable. Analysis is divided into two kinds of cases as transmission and distribution. To evaluate that Al conductor line has the insulation strength indeed safely, various analysis and calculation such as single line-to-ground fault current, lightning surge and allowance current were carried. Model was established based on real combined transmission and distribution is being used in utility with EMTP. The analysis results on Al and Cu conductor line were compared each other. It was proved that Al conductor line can be operated instead of Cu conductor line without special insulation problem in transmission and distribution, in electrical view point such as overvoltage and allowance current.