Title Modelling of Secondary Arc Using EMTP-RV
Authors 오윤식(Oh, Yun-Sik) ; 강성범(Kang, Sung-Bum) ; 서훈철(Seo, Hun-Chul) ; 김철환(Kim, Chul-Hwan)
DOI https://doi.org/10.5370/KIEE.2012.61.7.937
Page pp.937-943
ISSN 1975-8359
Keywords Auto reclosing ; EMTP-RV ; Secondary arc ; Transmission system
Abstract Most of faults occurred in transmission lines are single-phase to ground faults and transient faults. Single-phase auto reclosing is an appropriate scheme to maintain the system stability and restore the system effectively when those faults are occurred. In single-phase auto reclosing scheme, the secondary arc is generated after faulted phase is tripped to eliminate the fault and it is sustained by the capacitive and inductive coupling to the healthy phases. It is important to reclose the faulted phase after fully extinction of secondary arc because of the damage applied to system. Therefore, it is necessary to research on the detection of secondary arc extinction to ensure high success rate of reclosing. In this step, firstly, the accurate modelling of secondary arc should be performed. In this paper, the modelling of secondary arc is performed by using EMTP-RV and the simulation results show that the implemented model is correct and effective.