Title Analysis on the Operation Characteristics and Protection Coordination between the Current Ratio Differential Relay for Line Protection and the Trigger-type SFCL in the Power Transmission System
Authors 조용선(Cho, Yong-Sun) ; 김진석(Kim, Jin-Seok) ; 임성훈(Lim, Sung-Hun) ; 김재철(Kim, Jae-Chul)
DOI https://doi.org/10.5370/KIEE.2013.62.7.925
Page pp.925-930
ISSN 1975-8359
Keywords Superconducting fault current limiter (SFCL) ; Current ratio differential relay ; Power transmission system
Abstract The fault current of the power transmission system is greater than that of the power distribution system. Therefore, the introduction of superconducting fault current limiter (SFCL) is more needed to reduce the increased fault current. The trigger-type SFCL consists of the high-temperature superconducting element (HTSC), the current limiting reactor (CLR) and the circuit breaker (CB). The trigger-type SFCL can be used to supplement the disadvantages of the resistive-type SFCL. The operation characteristics of the current ratio differential relay which is usually applied to the protection device of the power transmission system are expected to be affected under fault conditions and the applicability of the trigger-type SFCL. In this paper, we analyzed the operating characteristics, by the fault conditions, between the current ratio differential relay for line protection and the trigger-type SFCL in the power transmission system through the PSCAD/EMTDC simulation.