• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Analysis of Effect on Lightning Surge according to the Grounding Condition of Overhead Ground Wire in Distribution System
Authors 한준(Han, Joon) ; 김철환(Kim, Chul-Hwan) ; 서훈철(Seo, Hun-Chul) ; 최선규(Choi, Sun-Kyu) ; 이병성(Lee, Byung-Sung)
DOI https://doi.org/10.5370/KIEE.2014.63.3.331
Page pp.331-337
ISSN 1975-8359
Keywords EMTP ; Flashover rate ; Grounding condition ; Lightning surge ; Overhead ground wire ; Overvoltage
Abstract The Korean distribution system consists of overhead ground wire (OHGW), phase conductors and neutral wire. Especially, OHGW is installed over the phase conductors to protect distribution system from the lightning surge. The flashover rate and the magnitude of lightning overvoltage on distribution system can be affected by grounding condition of OHGW such as grounding resistance and grounding interval. In this paper, we conduct an analysis of lightning overvoltage and flashover rate according to the grounding condition of OHGW. The distribution system and lightning surge are modeled by using ElectroMagnetic Transient Program (EMTP). Also, the Monte Carlo method is applied to consider random characteristics of lightning, and the flashover rate is calculated based on IEEE std. 1410. The simulations are performed by changing the grounding resistance and interval of OHGW and the simulation results are analyzed.