• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Effectiveness Evaluation According to Change of IJ Joint Box Location and Grounding System in Underground Transmission System
Authors 고광만(Ko, Kwang-Man) ; 이종범(Lee, Jong-Beom)
DOI https://doi.org/10.5370/KIEE.2015.64.2.247
Page pp.247-253
ISSN 1975-8359
Keywords Normal Joint(NJ) ; Insulation Joint(IJ) ; Service Entrance ; Sheath Component ; EMTP/ATPDraw
Abstract Dielectric breakdown accidents have been mainly occurred in the vicinity of service entrance section in underground power transmission systems. One cause among them is due to the excessive component value of sheath located around service entrance of cable. In this paper, as one of the alternative to prevent these accidents, the change of cross bond grounding system and the location change of IJ(Insulation Joint) are suggested. Also, to evaluate effectiveness of this changing system, circulating current and induced voltage of sheath were analyzed in steady and transient state. By comparison of the analytical results for the several possible changing systems, a grounding system and location of IJ which has the smallest sheath component values is proposed. In this paper, analysis to evaluate the proposed system is carried out by EMTP/ATPDraw. It can be used as a valuable operational material to prevent accident of the service entrance section in underground power transmission system.