• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Using the TDR in Dielectric for Partial Discharge Signals Detection Method
Authors 최문규(Choi, Mun-Gyu) ; 차한주(Cha, Hanju)
DOI https://doi.org/10.5370/KIEE.2015.64.9.1374
Page pp.1374-1379
ISSN 1975-8359
Keywords UHF ; Partial discharge ; TDR ; Dielectric
Abstract Time Domain Reflectometry(TDR) using microwave bands, including broadband spectrum that occurs at the range of rates that start between partial discharge position it easier to make the techniques that could be measured. Partial discharge in the Gas Insulated Switchgear(GIS), the dielectric constant in the band more than GHz different the insulating material if you want to organize, and the insulating material regardless of how partial discharge position in the SF6 gas Partial Discharge by applying the heritability estimated its position, but the position error occurred about 23 percent of the existing way, correct in not suitable location tracking the outbreak PD. This technique the rate of other dielectric that make up the power apparatus heterology is measured at the function to slow the progression of the electromagnetic waves apart by calculating the partial discharge as the location, A simple way to track. Dielectric using other methods proposed new structure can calculate the speed of heritability PD is occurring can measure.