Title Zero Sequence Impedance of Yg-Yg Three Phase Core Type Transformer
Authors 조현식(Jo, Hyunsik) ; 조성우(Cho, Sungwoo) ; 신창훈(Shin, Changhoon) ; 차한주(Cha, Hanju)
DOI https://doi.org/10.5370/KIEE.2016.65.6.940
Page pp.940-945
ISSN 1975-8359
Keywords Three phase core-type transformer ; Zero sequence impedance
Abstract In this paper, zero sequence equivalent circuit of Yg-Yg three phase core-type transformer is analyzed. Many problems by iron core structure of the three phase transformer due to asymmetric three phase lines, which includes line disconnection, ground fault, COS OFF, and unbalanced load are reported in the distribution system. To verify a feasibility of zero sequence impedance of Yg-Yg type three phase transformer, fault current generation in the three phase core and shell-type Yg-Yg transformer is compared by PSCAD/EMTDC when single line ground fault is occurred. As a result, shell-type transformer does not affect the flow of fault current, but core-type transformer generate an adverse effect by the zero sequence impedance. The adverse effect is explained by the zero sequence equivalent circuit of core-type transformer and Yg-Yg type three phase core-type transformer supplies a zero sequence fault current to the distribution system.