Title Complex Vector Current Control of Grid Connected Inverter Robust for Inductance Variation
Authors 이태진(Lee, Taejin) ; 조종민(Jo, Jongmin) ; 신창훈(Shin, Changhoon) ; 차한주(Cha, Hanju)
DOI https://doi.org/10.5370/KIEE.2016.65.10.1648
Page pp.1648-1654
ISSN 1975-8359
Keywords Cross-coupling ; Complex vector PI current controller ; Parameter variation ; Grid-connected
Abstract This paper analyzes complex vector current control for the enhanced cross-coupling compensation in accordance with parameter variation in grid-connected inverter system, and verifies through simulation and experiment. Complex vector current control is performed in the synchronous reference frame through d-q transformation. It generates cross-coupling components with rotating nominal angular frequency. In general, cross-coupling elements are compensated by decoupling terms added to output of conventional decoupling PI controller. But, it is impossible to compensate them perfectly which transient response is especially deteriorated such as large overshoot and slow tracking, when variation of grid impedance or measurement error occurs. However, complex vector current control can improve stability and response characteristic of current control regardless of the situation as before. Decoupling controller and complex vector controller are represented through complex forms, and these controllers are analyzed by using frequency response in s-domain, respectively. It is verified that complex vector controller has more superior response characteristic than decoupling controller through MATALB, PSIM and experimental in 5kW grid-connected inverter when L filter parameter is varied from 1.1mH to increase double, 2.2mH.