Title A Study on the Protective Coordination of Generator Overexcitation and Overvoltage Relay
Authors 박지경(Park, Ji-Kyung) ; 김광현(Kim, Kwnag-Hyun) ; 김철환(Kim, Chul-Hwan) ; 유영식(Lyu, Young-Sik) ; 양정재(Yang, Jeong-Jae)
DOI https://doi.org/10.5370/KIEE.2017.66.8.1187
Page pp.1187-1194
ISSN 1975-8359
Keywords AVR Protective Function ; Generator Protection System ; Overvoltage Relay ; Overexcitation Relay ; Protective Coordination
Abstract After North American wide area black out on August 14, 2003, various studies have been conducted to find out the reason of the disaster. One of main reasons was misoperation of generator protection system. Since then, protective coordination between generator protection system and excitation system controls has been hot issue among electrical engineers. Among various generator protection relays, in this paper, we focused on generator overvoltage and overexcitation relay, which protect the over-flux condition of the generator. Thus, at first, we modeled the generator overvoltage, overexcitation relay and detailed power system including excitation system, governor and etc., based on actual field data. And then, we reviewed the protective coordination of generator overvoltage and overexcitation relay using electromagnetic transient program. In addition, we discussed the protective coordination method for redundant protection relays in both automatic voltage regulator and generator side.