Title A Study on PI Observer Design for Line Fault Detection of a Single Machine Infinite Bus System
Authors 장수영(Su Young Jang) ; 김준우(Jun Woo Kim) ; 손영익(Young Ik Son) ; 남순열(Soon Ryul Nam) ; 강상희(Sang Hee Kang)
DOI https://doi.org/10.5370/KIEE.2019.68.10.1184
Page pp.1184-1188
ISSN 1975-8359
Keywords Line fault detection; PI observer; Out-of-Step; Swing equation; Single-machine infinite-bus power system
Abstract If a failure occurs in the power system; the electrical output of the generator changes; which can be regarded as a result of an external disturbance input. This paper presents a fault detection method and its application to the out-of-step protection problem by using a PI observer that estimates the magnitude of the disturbance. The performance of the designed observer is verified by computer simulations of the single-machine infinite bus power system. Simulation results show that the disturbance can be estimated successfully within the critical fault clearing time and the estimated disturbance can be used to predict whether the system maintains synchronization after the operation of the circuit breaker.