• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Analysis of Proper Frequency Range for Partial Discharge Diagnosis in Distribution Gas Insulated Switchgear
Authors 고현상(Hyeonsang Ko) ; 윤성호(Seongho Yoon) ; 김정태(Jeongtae Kim)
DOI https://doi.org/10.5370/KIEE.2019.68.11.1382
Page pp.1382-1388
ISSN 1975-8359
Keywords Distribution grade gas insulated switchgear; Partial discharge; Noise; Frequency characteristics
Abstract In order to improve the accuracy of partial discharge diagnosis by distinguishing internal partial discharge and external noises in distribution grade SF6 gas-insulated switchgear, partial discharges were measured for the on-site operated switchgears. Floating discharges due to water immersion defect in bushing, SF6 gas leakage defect, poor conductor-contact defect etc. were considered as internal discharges, and discharge by peeling semi-conductor paint in bushing was considered as external discharge. As a result, the main frequency bands of internal and external discharges were identified, and it was proposed that frequency bands of the partial discharge sensor would be designed in the range from 250MHz to 350MHz for detecting internal partial discharges.