Title A Study on Improvement of IEC 61850-Based Substation Restoration Scheme for Minimizing Outage Area in case of Breaker Failure
Authors 김민수(Min-Soo Kim) ; 강상희(Sang-Hee Kang)
DOI https://doi.org/10.5370/KIEE.2020.69.3.396
Page pp.396-401
ISSN 1975-8359
Keywords IEC 61850; Substation restoration; Breaker failure; Disconnect switch
Abstract This paper presents a study on improvement of IEC 61850-based substation restoration scheme for minimizing outage area in case of breaker failure. It utilizes voltage, current, and contact information of each circuit breaker and disconnect switch of transmission line and bus. In the event of a fault on a transmission line or a transformer or a bus, the IEC 61850-based substation restoration scheme for minimizing outage area proposed in this paper is explained, assuming that a breaker failure of a line or transformer has occurred, and the bus breakers are fully opened.