Title Design Method of Low-Voltage Wiring for Preventing Cable Burnout Owing to Over-current
Authors 연기용(Ki-Yong Yeon) ; 김동규(Dong-Kyu Kim) ; 이현명(Hyeon-Myeong Lee) ; 김재언(Jae-Eon Kim)
DOI https://doi.org/10.5370/KIEE.2020.69.8.1255
Page pp.1255-1262
ISSN 1975-8359
Keywords Low-Voltage Wiring; Over-current; Cable Design; Low-Voltage Line; Burnout
Abstract The Korea Electro-Technical Code (KEC) was enacted in March 2018 to meet international standards and develop the country's power industry, and will be implemented in January 2021. In KEC, the protection coordination between the cable and protection devices was to be in accordance with KS C IEC 60364. In this paper, I propose the design of protection coordination between cable and protection devices applying KS C IEC 60364 to draw out the problems of the design method based on the Technical Regulation in Electricity Business Act. In addition, the application method of demand factor for economical low-voltage wiring design was proposed. For the verification of the proposed design method, the design of low-voltage wiring in a certain apartment complex was modeled, and the analysis applied with the Technical Regulation in Electricity Business Act and KS C IEC 60364 was performed.
Finally, it is expected that this paper is utilized as a reference for designing economical and reasonable low-voltage wiring.