• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Detection Performance of 220-V, 60-Hz Series Arcs Within the Clearing Time Using a UVC Sensor
Authors 조윤진(Yun-Jin Cho) ; 조동일(Dong-Il Cho) ; 남준혁(Jun-Hyuk Nam) ; 문준선(Joon-Sun Moon) ; 한성호(Seong-Ho Han) ; 문원식(Won-Sik Moon)
DOI https://doi.org/10.5370/KIEE.2025.74.12.2411
Page pp.2411-2418
ISSN 1975-8359
Keywords Arc-fault detection; Series AC arc; UVC sensor; IEC 62606 clearing time; Event density
Abstract IEC 62606-aligned observation windows were used to evaluate 220V, 60Hz series arcs with synchronized three-channel measurements of voltage, current, and UVC. Arc currents of 2.5, 5, 10, and 16A were mapped to windows of 1.00, 0.50, 0.25, and 0.15s, respectively, and each case was repeated five times to compute the number of UVC events exceeding a fixed threshold within the window and the count density ??=??/??. The mean counts were 71.6, 66.0, 71.6, and 72.0, showing near invariance, with coefficients of variation of 5?8%. In contrast, the densities increased monotonically to 71.6, 132, 286.4, and 480s?1. Waveforms confirmed the simultaneous occurrence of current distortion and UVC pulse trains at ignition. Consequently, constant total counts with increasing density was empirically observed, and the clearing-time alignment with a single fixed threshold provides a reproducible benchmark for fair comparison of sensors and algorithms.