Title Islanding Detection Method for Grid-Forming InverterUsing Voltage Reference Perturbation
Authors 최예진(Yejin Choi) ; 정승민(Seungmin Jung) ; 유연태(Yeuntae Yoo)
DOI https://doi.org/10.5370/KIEE.2026.75.4.784
Page pp.784-790
Keywords Grid-Forming; Islanding Detection Method; Voltage Reference Perturbation; Rate of Change of Frequency; Short Circuit Ratio
Abstract Traditional islanding detection methods have been developed for the grid-following inverters. However, these methods are not directly applicable to grid-forming inverters because they regulate voltage and frequency. This paper proposes an islanding detection method specifically desinged for grid-forming inverters. Unintentional islanding scenarios are simulated using PSCAD/EMTDC witin the IEEE Std. 929-2000 test system. The proposed approach initially detects abnormal conditions by monitoring the rate of change of frequency. Subsequently, the voltage reference of the grid-forming inverter is finely adjusted within the nomial voltage range to determine whether the inverter operates in islanding mode. This perturbation-based method can distinguish islanding events from non-islanding transients such as faults.